Product search
VTB DN20 T20-70 Condenser Set
Recommended accessories
Thermostatic head setting limit999920 |
Configure product variant
Performance class
V'max[60mbar] = 1.1m³/h
Q'max = 26kW [20K]
Product documentation
Tender text
Baunach article master data Version: 19.11.24
BAFA funding opportunity within the scope of heating system optimisation through hydraulic balancing and installation of technology for volume flow control
Thermostatic flow temperature limiter with adjustable minimum temperature, with approx. 1% fixed minimum flow rate
For automatic, hydraulic balancing of downstream condensing exhaust gas heat exchangers of boilers and CHP units, especially in conjunction with our rMIX DN25 3×3 C loading station.
consisting of:
1) Valve body active opening VUO D 200 with fixed minimum flow DN20
Kvs = 4.6
V'max [60mbar] = 1.1m³/h
Q'max = 26kW [20K]
EPDM seal, inlet nipple R¾×Rp¾ outlet socket
conical screw connection G1 PN 10bar, Tmax 120°C on the inlet side (part no. 996 004)
2) Thermostatic head with spiral immersion sensor TK-WTF
Setpoint range 20°C to 70°C
Capillary tube length 2m Capillary tube seal Compression fitting R½
Coil immersion sensor length 125mm, reaction time approx. 5s
ATTENTION: Immersion sensor touches heating water - provide shut-off on site!
PN 10bar, Tmax 90°C (part no. 996 005)
3) T-piece black, TsF ¾x¾x½ (part no. 996 055)
Performance data
Kvs = 4.6, V'max [60mbar] = 1.1m³/h, Q'max = 26kW [20K]