Product search
RTB DN50s T25-70 Adjustment Set
Configure product variant
Performance class
V'max[100mbar] = 6.3m³/h
Q'max = 150kW [20K] = 60l/min [10/45°C]
Product documentation
Tender text
Baunach article master data Version: 19.11.24
BAFA funding opportunity within the scope of heating system optimisation through hydraulic balancing and installation of technology for volume flow control
Thermostatic return temperature limiter with adjustable maximum temperature, with approx. 1% fixed minimum flow rate
For automatic hydraulic balancing of individual heat exchangers such as domestic hot water storage tanks, air heaters, swimming pool heat exchangers and ventilation and air conditioning systems.
consisting of:
1) Valve lower section actively closing VUS D 500 with approx. 1% fixed minimum flow rate
DN50, DpN 100mbar, V'maxN 6,3m³/h, Kvs 20, straight pattern, gunmetal
External thread, PN 8bar, Tmax 200°C
2) Thermostatic head with immersion sensor
Setpoint range 25°C to 70°C
Capillary tube length 2m, capillary tube seal compression fitting R¾
Sensor dimension 16x210mm
3) Immersion sleeve HSF R¾×220mm
4) 2x screw nipple insert, flat sealing, R2
Performance data
DN50, DpN 100mbar, V'maxN 6,3m³/h, Kvs 20, straight pattern, gunmetal