Product search
DUVbox DN25 2x4 L 3
Configure product variant
Nominal width
Performance class
Kvs = 9.4 V'max[250mbar] = 4.7m³/h
Q'max[20K] = 109kW Q'max[10K] = 55kW
Flow direction producer
Pump flange
Product documentation
Assembly instructions
Assembly instructions: For specialist partners only.
Please log in here or register here
Actuator three-way mixer: For specialist partners only.
Please log in here or register here
Spare parts drawing
Spare parts drawing For specialist partners only.
Please log in here or register here
Data sheet
GAEB
Tender text
Baunach article master data Version: 19.11.24
BAFA funding opportunity as part of heating system optimisation through hydraulic balancing and installation of separate control technology
rendeMIX double changeover valve consisting of two 3-way changeover valves DN32×G1½(a) Ms58, plug and cover Ms58
For highly efficient two-zone charging of a buffer storage tank by a heat generator with minimum circulation in heating mode and with priority hot water preparation
2 actuators EMS 90-2P, 230V~ 50Hz 2.3VA 2-point signal, 6Nm (240h), 90°, 60s, left closing, grey adapter
Switching assembly with 4 connections to the buffer tank, CuØ35×1, pipe spacing to the heat generator 200mm, pipe spacing to the buffer tank 100mm, DN32×G1½(a) flat
1 integrated gravity brake/backflow preventer, Dp10mbar
Generator circuit (LT): Kvs = 9.4 - V'max[250mbar] = 4.7m³/h - Q'max[20K] = 109kW - Q'max[10K] = 55kW - Leakage rate < 0,1%
6 Thermometers 0-120°C, Ø63mm, soldering sleeves Ms58
6 ball valve unions, DN25 passage, PN32, G1½(i)×Rp1 flat-sealing, stuffing box, sealing hole, spindle with aluminium wing handle
Insulating moulded tray EPP 40g/l, black, 450×450mm, quick assembly kit
With pump flange G1½(i) for pump DN25 on the unmixed heating circuit flow (3)
Assembly does NOT include pump compensator - PAS L180 (Part No.: 001 338)
Assembly does not contain a pump
Model DN 25 - light version, PN 10bar, Tmax 120°C
Performance data
Generator circuit (LT): Kvs = 9.4 - V'max[250mbar] = 4.7m³/h - Q'max[20K] = 109kW - Q'max[10K] = 55kW - Leakage rate < 0,1%