rMIX DN32 2x4+UV R

Item no. 001 131 Return flow utilisation
For highly efficient use of the return flow of an unmixed high-temperature circuit (charging circuit) controlled via a changeover valve in a mixed low-temperature circuit (mixing circuit) on a condensing boiler with minimum circulation

Recommended accessories

								

Schl KuH DN32-50 set

996167
								

ISO KuH DN32 G1½(i)xRp1¼

996086

Further information?

Further questions?

Contact technical support
					

Configure product variant

Nominal width

DN32

Flow direction producer

Flow direction Producer Right

Product documentation

Assembly instructions

Assembly instructions: For specialist partners only.
Please log in here or register here

Actuator multi-way mixer: For specialist partners only.
Please log in here or register here

Actuator three-way mixer: For specialist partners only.
Please log in here or register here

GAEB

001131.D81

Tender text

Baunach article master data Version: 19.11.24

BAFA funding opportunity as part of heating system optimisation through hydraulic balancing and installation of separate control technology

rendeMIX multi-port mixing manifold with 3/3-way tangential mixing valve DN32×G1½(a) MsGuss (red adapter) and 3-way mixing valve DN32×G1½(a) Ms58, plug and cover Ms58

For highly efficient use of the return flow of an unmixed high-temperature circuit (charging circuit) controlled via a changeover valve in a mixed low-temperature circuit (mixing circuit) on a condensing boiler with minimum circulation

Charging circuit: EMS 90-2P actuator, 230V~ 50Hz 2.3VA 2-point signal, 6Nm (240h), 90°, 60s, left closing, grey adapter. Mixing circuit: EMS 240 actuator, 230V~ 50Hz 3.5VA 3-point signal, 5Nm (240h), 240°, 93s

Dual circuit manifold assembly with 2 connections to the heat source and 4 connections to the heat sinks, CuØ35×1, DN32×G1½(a) flat, pipe spacing 100mm.

2 integrated gravity brakes/backflow preventer, Dp10mbar

Charging circuit (HT): Kvs = 13.6 • V'max[100mbar] = 4.3m³/h • Q'max[20K] = 100kW • Leakage rate < 0.1% - Mixing circuit (NT): Kvs = 18.9 • V'max[100mbar] = 6m³/h • Q'max[10K] = 70kW • Leakage rate < 0,1%

6 Thermometers 0-120°C, Ø63mm, soldering sleeves Ms58

6 ball valve screw connections, DN32 passage, PN25, G1½(i)×Rp1¼ flat-sealing, stuffing box, spindle with square drive SW25

Insulating moulded tray EPP 40g/l, black, 450×450mm, quick assembly kit

Without pump flanges

Assembly does NOT include pump compensator - PAS L180 (Part No.: 001 338)

Assembly does not contain a pump

Model DN 32, PN 10bar, Tmax 120°C

Performance data

Charging circuit (HT): Kvs = 13.6 • V'max[100mbar] = 4.3m³/h • Q'max[20K] = 100kW • Leakage rate < 0.1% - Mixing circuit (NT): Kvs = 18.9 • V'max[100mbar] = 6m³/h • Q'max[10K] = 70kW • Leakage rate < 0,1%

Baunach