Product search
rMIX DN32 2x4 R
Recommended accessories
Schl KuH DN32-50 set996167 |
ISO KuH DN32 G1½(i)xRp1¼996086 |
Configure product variant
Performance class
Kvs = 15,8 V'max[100mbar] = 5m³/h
Q'max[20K] = 116kW
Mixing circuit (LT):
Kvs = 18.9 V'max[100mbar] = 6m³/h
Q'max[10K] = 70kW
Flow direction producer
Product documentation
Assembly instructions
Assembly instructions: For specialist partners only.
Please log in here or register here
Actuator multi-way mixer: For specialist partners only.
Please log in here or register here
Spare parts drawing
Spare parts drawing For specialist partners only.
Please log in here or register here
Data sheet
GAEB
Tender text
Baunach article master data Version: 19.11.24
BAFA funding opportunity as part of heating system optimisation through hydraulic balancing and installation of separate control technology
rendeMIX multi-port mixing manifold with 3/3-way tangential mixing valve DN32×G1½(a) MsGuss (red adapter), plug and cover Ms58
For highly efficient use of the return flow of an unmixed high-temperature circuit in a mixed low-temperature circuit at a condensing boiler, a stratified tank or a heat transfer station.
Actuator EMS 240, 230V~ 50Hz 3.5VA 3-point signal, 5Nm (240h), 240°, 93s
Dual circuit manifold assembly with 2 connections to the heat source and 4 connections to the heat sinks, CuØ35×1, DN32×G1½(a) flat, pipe spacing 100mm.
3 integrated gravity brakes/backflow preventer, Dp10mbar
Direct heating circuit (HT): Kvs = 15.8 - V'max[100mbar] = 5m³/h - Q'max[20K] = 116kW - Mixed heating circuit (LT): Kvs = 18.9 - V'max[100mbar] = 6m³/h - Q'max[10K] = 70kW - Leakage rate < 0,1%
6 Thermometers 0-120°C, Ø63mm, soldering sleeves Ms58
6 ball valve screw connections, DN32 passage, PN25, G1½(i)×Rp1¼ flat-sealing, stuffing box, spindle with square drive SW25
Insulating moulded tray EPP 40g/l, black, 450×450mm, quick assembly kit
Without pump flanges
Assembly does NOT include pump compensator - PAS L180 (Part No.: 001 338)
Assembly does not contain a pump
Model DN 32, PN 10bar, Tmax 120°C
Performance data
Direct heating circuit (HT): Kvs = 15.8 - V'max[100mbar] = 5m³/h - Q'max[20K] = 116kW - Mixed heating circuit (LT): Kvs = 18.9 - V'max[100mbar] = 6m³/h - Q'max[10K] = 70kW - Leakage rate < 0,1%