rSYS DN25 2x4+3mix R 35

Item no. 001 593 Return flow utilisation
For discharging a stratified storage tank in a mixed low-temperature circuit (2nd mixed circuit) by means of high-efficiency operation of a system separation via flow control with highly efficient use of the return flow of a mixed high-temperature circuit (1st mixed circuit) with the lowest possible return flow temperature.

Accessories needed

								

ST DN25 AD100 P40 LR 5

001038
								

ST DN25 AD100 P40 LR

001036

Further information?

Further questions?

Contact technical support
					

Configure product variant

Nominal width

DN25

Performance class

1st mixing circuit (HT):
Kvs = 12.5 • V'max[100mbar] = 4m³/h
Q'max[20K] = 93kW
2nd mixing circuit (LT) with ST DN25:
Kvs = 5.7 • V'max[100mbar] = 1.8m³/h
Q'max[10K] = 21kW

Flow direction producer

Flow direction Producer Right

Pump flange

on the heating (3) and mixing circuit flow (5)

Product documentation

Assembly instructions

Assembly instructions: For specialist partners only.
Please log in here or register here

Actuator multi-way mixer: For specialist partners only.
Please log in here or register here

Actuator three-way mixer: For specialist partners only.
Please log in here or register here

Spare parts drawing

Spare parts drawing For specialist partners only.
Please log in here or register here

Data sheet

001593_DBL_2021-12-21.pdf

GAEB

001593.D81

Tender text

Baunach article master data Version: 19.11.24

BAFA funding opportunity as part of heating system optimisation through hydraulic balancing and installation of separate control technology

rendeMIX multi-port mixing manifold with 3/2-way tangential mixing valve DN25×G1½(a) MsGuss (red adapter) and 3-way mixing valve DN32×G1½(a) Ms58, plug and cover Ms58

For discharging a stratified storage tank in a mixed low-temperature circuit (2nd mixed circuit) by means of high-efficiency operation of a system separation via flow control with highly efficient use of the return flow of a mixed high-temperature circuit (1st mixed circuit) with the lowest possible return flow temperature.

1st mixing circuit: EMS 90-3P actuator, 230V~ 50Hz 3.5VA 3-point signal, 5Nm (240h), 90°, 70s, grey adapter. 2nd mixing circuit: EMS 240 actuator, 230V~ 50Hz 3.5VA 3-point signal, 5Nm (240h), 240°, 93s

Dual circuit manifold assembly with 2 connections to the heat source and 4 connections to the heat sinks, CuØ35×1, DN32×G1½(a) flat, pipe spacing 100mm.

2 integrated gravity brakes/backflow preventer, Dp10mbar

1. mixing circuit (HT): Kvs = 12.5 - V'max[100mbar] = 4m³/h - Q'max[20K] = 93kW - leakage rate < 0.1% - 2nd mixing circuit (NT) with ST DN25: Kvs = 5.7 • V'max[100mbar] = 1.8m³/h • Q'max[10K] = 21kW • Leakage rate < 0,1%

6 Thermometers 0-120°C, Ø63mm, soldering sleeves Ms58

6 ball valve unions, DN25 passage, PN32, G1½(i)×Rp1 flat-sealing, stuffing box, sealing hole, spindle with aluminium wing handle

Insulating moulded tray EPP 40g/l, black, 450×450mm, quick assembly kit

With pump flanges G1½(i) for pumps DN25 on the 1st mixed high (3) and on the 2nd mixed low temperature circuit flow (5).

Assembly includes ONE pump balancing piece - PAS L180 - with G1½(a)×G1½(i) fittings for balancing one pump DN25, length 180mm, insulated (part no.: 001 338).

Assembly does not contain a pump

Model DN 25 - light version, PN 10bar, Tmax 120°C

ATTENTION: CANNOT BE USED WITHOUT SYSTEM SEPARATION!

Performance data

1. mixing circuit (HT): Kvs = 12.5 - V'max[100mbar] = 4m³/h - Q'max[20K] = 93kW - leakage rate < 0.1% - 2nd mixing circuit (NT) with ST DN25: Kvs = 5.7 • V'max[100mbar] = 1.8m³/h • Q'max[10K] = 21kW • Leakage rate < 0,1%

Baunach