rSYS DN25s 2x4 LH 3-a

Item no. 001 652 Return flow utilisation
For highly efficient utilisation of the return flow of an unmixed high-temperature circuit in a mixed low-temperature circuit by means of highly efficient operation of a system separation via flow control at a condensing boiler, a stratified storage tank or a heat transfer station.

Accessories needed

								

ST DN25s AD100 P60 LL 5

001108
								

ST DN25s AD100 P60 LL

001106

Recommended accessories

								

ISO KuHV DN25s G1½(i)xRp1

996085

Further information?

Further questions?

Contact technical support
					

Configure product variant

Nominal width

DN25s

Performance class

Direct heating circuit (HT):
Kvs = 11.9 • V'max[100mbar] = 3.8m³/h
Q'max[20K] = 88kW
Mixing circuit (LT) with ST DN25s: Kvs = 7.2 • V'max[100mbar] = 2.3m³/h
Q'max[10K] = 27kW

Flow direction producer

Flow direction Producer Left

Product documentation

Assembly instructions

Assembly instructions: For specialist partners only.
Please log in here or register here

Actuator multi-way mixer: For specialist partners only.
Please log in here or register here

Spare parts drawing

Spare parts drawing For specialist partners only.
Please log in here or register here

Data sheet

001652_DBL_2020-09-17.pdf

GAEB

001652.D81

Tender text

Baunach article master data Version: 19.11.24

BAFA funding opportunity within the scope of heating system optimisation by replacing heating circulating pumps with high-efficiency circulating pumps.

rendeMIX multi-port mixing manifold with 3/2-way tangential mixing valve DN25×G1½(a) MsGuss (adapter red), plug and cover Ms58

For highly efficient utilisation of the return flow of an unmixed high-temperature circuit in a mixed low-temperature circuit by means of highly efficient operation of a system separation via flow control at a condensing boiler, a stratified storage tank or a heat transfer station.

Actuator EMS 240, 230V~ 50Hz 3.5VA 3-point signal, 5Nm (240h), 240°, 93s

Dual circuit manifold assembly with 2 connections to the heat source and 4 connections to the heat sinks, CuØ35×1, DN32×G1½(a) flat, pipe spacing 100mm.

3 integrated gravity brakes/backflow preventer, Dp10mbar

Direct heating circuit (HT): Kvs = 11.9 - V'max[100mbar] = 3.8m³/h - Q'max[20K] = 88kW - Mixed circuit (LT) with ST DN25s: Kvs = 7.2 - V'max[100mbar] = 2.3m³/h - Q'max[10K] = 27kW - Leakage rate < 0,1%

6 Thermometers 0-120°C, Ø63mm, soldering sleeves Ms58

6 ball valve screw connections, DN25s passage, PN20, G1½(i)×Rp1 flat-sealing, stuffing box, spindle with aluminium T-handle

Insulating moulded tray EPP 40g/l, black, 450×450mm, quick assembly kit

With pump flange G1½(i) for pump DN25 on the unmixed heating circuit flow (3)

Assembly includes ONE pump balancing piece - PAS L180 - with G1½(a)×G1½(i) fittings for balancing one pump DN25, length 180mm, insulated (part no.: 001 338).

With built-in high-efficiency Grundfos UPM3 pump, DN25, 130mm, H 5-6mWS, 230V~ 50Hz, 2m connection cable, EEI < 0,2

Model DN 25 - strong version, PN 10bar, Tmax 120°C

ATTENTION: CANNOT BE USED WITHOUT SYSTEM SEPARATION!

Performance data

Direct heating circuit (HT): Kvs = 11.9 - V'max[100mbar] = 3.8m³/h - Q'max[20K] = 88kW - Mixed circuit (LT) with ST DN25s: Kvs = 7.2 - V'max[100mbar] = 2.3m³/h - Q'max[10K] = 27kW - Leakage rate < 0,1%

Baunach