Product search
rSYS DN32 3x2 LR
Accessories needed
![]() |
ST DN32 AD200 P60 R 5001169 |
![]() |
ST DN32 AD200 P60 R001167 |
Recommended accessories
![]() |
Schl KuH DN32-50 set996167 |
|
ISO KuH DN32 G1½(i)xRp1¼996086 |
Configure product variant
Performance class
Kvs = 12.7 V'max[100mbar] = 4m³/h
Q'max[20K] = 93kW Q'max[10K] = 47kW
Flow direction producer
Flow direction consumer
Pump flange
Product documentation
Assembly instructions
Assembly instructions: For specialist partners only.
Please log in here or register here
Actuator multi-way mixer: For specialist partners only.
Please log in here or register here
Spare parts drawing
Spare parts drawing For specialist partners only.
Please log in here or register here
Data sheet
GAEB
Tender text
Baunach article master data Version: 19.11.24
BAFA funding opportunity as part of heating system optimisation through hydraulic balancing and installation of separate control technology
rendeMIX multi-port mixing manifold with 3/2-way tangential mixing valve DN32×G1½(a) MsGuss (adapter green), plug and cover Ms58
For highly efficient two-zone unloading of a buffer tank through a mixing circuit by means of highly efficient operation of a system separation via flow control
Actuator EMS 240, 230V~ 50Hz 3.5VA 3-point signal, 5Nm (240h), 240°, 93s
Single circuit mixer assembly with 3 connections to the heat source, CuØ35×1, DN32×G1½(a) flat, pipe distance to the heat source 100mm, pipe distance to the mixing circuit 200mm.
2 integrated gravity brakes/backflow preventer, Dp10mbar
Mixing circuit (LT) for system separation on site: Kvs = 12.7 - V'max[100mbar] = 4m³/h - Q'max[20K] = 93kW - Q'max[10K] = 47kW - Leakage rate < 0,1%
5 Thermometers 0-120°C, Ø63mm, soldering sleeves Ms58
5 Ball valve screw connections, DN32 passage, PN25, G1½(i)×Rp1¼ flat-sealing, stuffing box, spindle with square drive SW25
Insulating moulded tray EPP 40g/l, black, 300×450mm, quick assembly kit
Without pump flanges
Assembly does NOT include pump compensator - PAS L180 (Part No.: 001 338)
Assembly does not contain a pump
Model DN 32, PN 10bar, Tmax 120°C
ATTENTION: CANNOT BE USED WITHOUT SYSTEM SEPARATION!
Performance data
Mixing circuit (LT) for system separation on site: Kvs = 12.7 - V'max[100mbar] = 4m³/h - Q'max[20K] = 93kW - Q'max[10K] = 47kW - Leakage rate < 0,1%