Product search
rSYS DN25s 2x4+3mix R
Accessories needed
|
ST DN25s AD100 P60 LR 5001138 |
|
ST DN25s AD100 P60 LR001136 |
Recommended accessories
ISO KuHV DN25s G1½(i)xRp1996085 |
Configure product variant
Nominal width
Performance class
Kvs = 13.3 V'max[100mbar] = 4.2m³/h
Q'max[20K] = 98kW
2nd mixing circuit (LT) for ST on-site:
Kvs = 9.7 V'max[100mbar] = 3.1m³/h
Q'max[10K] = 36kW
Flow direction producer
Pump flange
Product documentation
Assembly instructions
Assembly instructions: For specialist partners only.
Please log in here or register here
Actuator multi-way mixer: For specialist partners only.
Please log in here or register here
Actuator three-way mixer: For specialist partners only.
Please log in here or register here
Spare parts drawing
Spare parts drawing For specialist partners only.
Please log in here or register here
Data sheet
GAEB
Tender text
Baunach article master data Version: 19.11.24
BAFA funding opportunity as part of heating system optimisation through hydraulic balancing and installation of separate control technology
rendeMIX multi-port mixing manifold with 3/2-way tangential mixing valve DN25×G1½(a) MsGuss (red adapter) and 3-way mixing valve DN32×G1½(a) Ms58, plug and cover Ms58
For discharging a stratified storage tank in a mixed low-temperature circuit (2nd mixed circuit) by means of high-efficiency operation of a system separation via flow control with highly efficient use of the return flow of a mixed high-temperature circuit (1st mixed circuit) with the lowest possible return flow temperature.
1st mixing circuit: EMS 90-3P actuator, 230V~ 50Hz 3.5VA 3-point signal, 5Nm (240h), 90°, 70s, grey adapter. 2nd mixing circuit: EMS 240 actuator, 230V~ 50Hz 3.5VA 3-point signal, 5Nm (240h), 240°, 93s
Dual circuit manifold assembly with 2 connections to the heat source and 4 connections to the heat sinks, CuØ35×1, DN32×G1½(a) flat, pipe spacing 100mm.
3 integrated gravity brakes/backflow preventer, Dp10mbar
1st mixing circuit (HT): Kvs = 13.3 - V'max[100mbar] = 4.2m³/h - Q'max[20K] = 98kW - leakage rate < 0.1% - 2nd mixing circuit (NT) for system separation on site: Kvs = 9.7 V'max[100mbar] = 3.1m³/h Q'max[10K] = 36kW Leakage rate < 0,1%
6 Thermometers 0-120°C, Ø63mm, soldering sleeves Ms58
6 ball valve screw connections, DN25s passage, PN20, G1½(i)×Rp1 flat-sealing, stuffing box, spindle with aluminium T-handle
Insulating moulded tray EPP 40g/l, black, 450×450mm, quick assembly kit
Without pump flanges
Assembly does NOT include pump compensator - PAS L180 (Part No.: 001 338)
Assembly does not contain a pump
Model DN 25 - strong version, PN 10bar, Tmax 120°C
ATTENTION: CANNOT BE USED WITHOUT SYSTEM SEPARATION!
Performance data
1st mixing circuit (HT): Kvs = 13.3 - V'max[100mbar] = 4.2m³/h - Q'max[20K] = 98kW - leakage rate < 0.1% - 2nd mixing circuit (NT) for system separation on site: Kvs = 9.7 V'max[100mbar] = 3.1m³/h Q'max[10K] = 36kW Leakage rate < 0,1%