rJET DN25 3x4 R 1

Item no. 001 295 Two-zone discharge
For highly efficient two-zone unloading of a buffer tank in a mixed low-temperature circuit by means of highly efficient operation of a system separation via flow control from the differential pressure of the pump in the heat generator circuit (i.e. without an additional pump in the primary circuit of the system separation!) with highly efficient use of the return flow of an unmixed high-temperature circuit.

Accessories needed

								

ST DN25 AD100 P40 LR 5

001038
								

ST DN25 AD100 P40 LR

001036

Further information?

Further questions?

Contact technical support
					

Configure product variant

Nominal width

DN25

Performance class

Direct heating circuit (HT):
Kvs = 5.6 • V'max[100mbar] = 1.8m³/h
Q'max[20K] = 42kW
Mixing circuit (LT) with ST DN25:
Kvs = 5.7 • V'max[100mbar] = 1.8m³/h
Q'max[10K] = 21kW

Flow direction producer

Flow direction Producer Right

Pump flange

on the heat generator flow (1)

Product documentation

Assembly instructions

Assembly instructions: For specialist partners only.
Please log in here or register here

Actuator multi-way mixer: For specialist partners only.
Please log in here or register here

Spare parts drawing

Spare parts drawing For specialist partners only.
Please log in here or register here

Data sheet

001295_DBL_2019-10-08.pdf

GAEB

001295.D81

Tender text

Baunach article master data Version: 19.11.24

BAFA funding opportunity as part of heating system optimisation through hydraulic balancing and installation of separate control technology

rendeMIX multi-port mixing manifold with 3/2-way tangential mixing valve DN25×G1½(a) MsGuss (adapter red), plug and cover Ms58

For highly efficient two-zone unloading of a buffer tank in a mixed low-temperature circuit by means of highly efficient operation of a system separation via flow control from the differential pressure of the pump in the heat generator circuit (i.e. without an additional pump in the primary circuit of the system separation!) with highly efficient use of the return flow of an unmixed high-temperature circuit.

Actuator EMS 240, 230V~ 50Hz 3.5VA 3-point signal, 5Nm (240h), 240°, 93s

Two-circuit manifold assembly with 3 connections to the heat generator (buffer or boiler with flue gas heat exchanger), CuØ35×1, pipe spacing 100mm, DN32×G1½(a) flat

1 integrated backflow preventer, Dp10mbar and 1 integrated return differential pressure regulator, Dp50-70mbar

Direct heating circuit (HT): Kvs = 5.6 - V'max[100mbar] = 1.8m³/h - Q'max[20K] = 42kW - Mixed heating circuit (LT) with ST DN25: Kvs = 5.7 - V'max[100mbar] = 1.8m³/h - Q'max[10K] = 21kW - Leakage rate < 0,1%

7 Thermometer 0-120°C, Ø63mm, soldering sleeves Ms58

7 Ball valve screw connections, DN25, PN32, G1½(i)×Rp1 flat-sealing, stuffing box, sealing hole, spindle with aluminium wing handle

Insulating moulded tray EPP 40g/l, black, 450×450mm, quick assembly kit

With pump flange G1½(i) for pump DN25 on heat generator flow (1)

Assembly does NOT include pump compensator - PAS L180 (Part No.: 001 338)

Assembly does not contain a pump

Model DN 25 - light version, PN 10bar, Tmax 120°C

ATTENTION: CANNOT BE USED WITHOUT SYSTEM SEPARATION!

Performance data

Direct heating circuit (HT): Kvs = 5.6 - V'max[100mbar] = 1.8m³/h - Q'max[20K] = 42kW - Mixed heating circuit (LT) with ST DN25: Kvs = 5.7 - V'max[100mbar] = 1.8m³/h - Q'max[10K] = 21kW - Leakage rate < 0,1%