Product search
rSYS DN25 3x2 LR 5
Accessories needed
![]() |
ST DN25 AD100 P40 RR 5001009 |
![]() |
ST DN25 AD100 P40 RR001007 |
Configure product variant
Performance class
Kvs = 5.7 V'max[100mbar] = 1.8m³/h
Q'max[20K] = 42kW Q'max[10K] = 21kW
Flow direction producer
Flow direction consumer
Pump flange
Product documentation
Assembly instructions
Assembly instructions: For specialist partners only.
Please log in here or register here
Actuator multi-way mixer: For specialist partners only.
Please log in here or register here
Spare parts drawing
Spare parts drawing For specialist partners only.
Please log in here or register here
Data sheet
GAEB
Tender text
Baunach article master data Version: 19.11.24
BAFA funding opportunity as part of heating system optimisation through hydraulic balancing and installation of separate control technology
rendeMIX multi-port mixing manifold with 3/2-way tangential mixing valve DN25×G1½(a) MsGuss (adapter green), plug and cover Ms58
For highly efficient two-zone unloading of a buffer tank through a mixing circuit by means of highly efficient operation of a system separation via flow control
Actuator EMS 240, 230V~ 50Hz 3.5VA 3-point signal, 5Nm (240h), 240°, 93s
Single circuit mixer assembly with 3 connections to the heat source, CuØ35×1, DN32×G1½(a) flat, pipe spacing 100mm.
1 integrated gravity brake/backflow preventer, Dp10mbar
Mixing circuit (NT) with ST DN25: Kvs = 5.7 V'max[100mbar] = 1.8m³/h Q'max[20K] = 42kW Q'max[10K] = 21kW Leakage rate < 0,1%
5 Thermometers 0-120°C, Ø63mm, soldering sleeves Ms58
5 Ball valve screw connections, DN25, PN32, G1½(i)×Rp1 flat-sealing, stuffing box, sealing hole, spindle with aluminium wing handle
Insulating moulded tray EPP 40g/l, black, 300×450mm, quick assembly kit
With pump flange G1½(i) for pump DN25 at the mixing circuit flow (5)
Assembly includes ONE pump balancing piece - PAS L180 - with G1½(a)×G1½(i) fittings for balancing one pump DN25, length 180mm, insulated (part no.: 001 338).
Assembly does not contain a pump
Model DN 25 - light version, PN 10bar, Tmax 120°C
ATTENTION: CANNOT BE USED WITHOUT SYSTEM SEPARATION!
Performance data
Mixing circuit (NT) with ST DN25: Kvs = 5.7 V'max[100mbar] = 1.8m³/h Q'max[20K] = 42kW Q'max[10K] = 21kW Leakage rate < 0,1%