rSYS DN25s 2x4+UV L 5

Item no. 001 668 Return flow utilisation
For the highly efficient use of the return flow of an unmixed high-temperature circuit (charging circuit) controlled via a changeover valve in a mixed low-temperature circuit (mixing circuit) by means of highly efficient operation of a system separation via flow control on a condensing boiler with minimum circulation

Accessories needed

								

ST DN25s AD100 P60 RL 5

001139
								

ST DN25s AD100 P60 RL

001137

Recommended accessories

								

ISO KuHV DN25s G1½(i)xRp1

996085

Further information?

Further questions?

Contact technical support
					

Configure product variant

Nominal width

DN25s

Performance class

Charging circuit (HT):
Kvs = 13.3 • V'max[100mbar] = 4.2m³/h
Q'max[20K] = 98kW
Mixing circuit (LT) with ST DN25s:Kvs = 7.2 • V'max[100mbar] = 2.3m³/h
Q'max[10K] = 27kW

Flow direction producer

Flow direction Producer Left

Product documentation

Assembly instructions

Assembly instructions: For specialist partners only.
Please log in here or register here

Actuator multi-way mixer: For specialist partners only.
Please log in here or register here

Actuator three-way mixer: For specialist partners only.
Please log in here or register here

Spare parts drawing

Spare parts drawing For specialist partners only.
Please log in here or register here

Data sheet

001668_DBL_2020-08-26.pdf

GAEB

001668.D81

Tender text

Baunach article master data Version: 10.05.24

BAFA funding opportunity as part of heating system optimisation through hydraulic balancing and installation of separate control technology

rendeMIX multi-port mixing manifold with 3/2-way tangential mixing valve DN25×G1½(a) MsGuss (adapter green) and 3-way mixing valve DN32×G1½(a) Ms58, plug and cover Ms58

For the highly efficient use of the return flow of an unmixed high-temperature circuit (charging circuit) controlled via a changeover valve in a mixed low-temperature circuit (mixing circuit) by means of highly efficient operation of a system separation via flow control on a condensing boiler with minimum circulation

Charging circuit: EMS 90-2P actuator, 230V~ 50Hz 2.3VA 2-point signal, 6Nm (240h), 90°, 60s, right-hand closing, grey adapter. Mixing circuit: EMS 240 actuator, 230V~ 50Hz 3.5VA 3-point signal, 5Nm (240h), 240°, 93s

Dual circuit manifold assembly with 2 connections to the heat source and 4 connections to the heat sinks, CuØ35×1, DN32×G1½(a) flat, pipe spacing 100mm.

2 integrated gravity brakes/backflow preventer, Dp10mbar

Charging circuit (HT): Kvs = 13.3 • V'max[100mbar] = 4.2m³/h • Q'max[20K] = 98kW • Leakage rate < 0.1% - Mixing circuit (NT) with ST DN25s: Kvs = 7.2 • V'max[100mbar] = 2.3m³/h • Q'max[10K] = 27kW • Leakage rate < 0,1%

6 Thermometers 0-120°C, Ø63mm, soldering sleeves Ms58

6 ball valve screw connections, DN25s passage, PN20, G1½(i)×Rp1 flat-sealing, stuffing box, spindle with aluminium T-handle

Insulating moulded tray EPP 40g/l, black, 450×450mm, quick assembly kit

With pump flange G1½(i) for pump DN25 at the mixing circuit flow (5)

Assembly includes ONE pump balancing piece - PAS L180 - with G1½(a)×G1½(i) fittings for balancing one pump DN25, length 180mm, insulated (part no.: 001 338).

Assembly does not contain a pump

Model DN 25 - strong version, PN 10bar, Tmax 120°C

ATTENTION: CANNOT BE USED WITHOUT SYSTEM SEPARATION!

Performance data

Charging circuit (HT): Kvs = 13.3 • V'max[100mbar] = 4.2m³/h • Q'max[20K] = 98kW • Leakage rate < 0.1% - Mixing circuit (NT) with ST DN25s: Kvs = 7.2 • V'max[100mbar] = 2.3m³/h • Q'max[10K] = 27kW • Leakage rate < 0,1%

Baunach